AS/NZS 3760 test and tag intervals explained

AS/NZS 3760 is the standard that drives test and tag in Australian workplaces. Here is how the intervals are set, where 3 months is required vs where 12 months is enough, and how to keep a register the regulator will accept.

6 min readUpdated 23 June 2026

What AS/NZS 3760 covers (and what it does not)

AS/NZS 3760 — In-service inspection and testing of electrical equipment — is the joint Australia/New Zealand standard that defines how portable electrical equipment is inspected and tested after it leaves the manufacturer and is in service. It covers visual inspection, electrical safety tests (earth continuity, insulation resistance, polarity, leakage current) and the documentation that goes with them.

It does not cover fixed wiring (that is AS/NZS 3000), and it is not a regulatory document on its own — it is the technical standard that workplace safety regulators reference when they say electrical equipment must be safe to use.

Recommended intervals by environment

AS/NZS 3760 sets test and inspection intervals based on the environment the equipment works in. Harsher environments (construction sites, factories with vibration, dust or moisture) need shorter intervals; offices and similar low-risk environments need longer ones.

The common intervals you will encounter in Perth workplaces:

  • Construction, demolition and like environments — 3 months
  • Factories, workshops, warehouses and similar — 6 months
  • Commercial cleaning equipment — 6 months
  • Hire equipment — inspection before each hire; test every 12 months
  • Offices, shops, low-risk commercial environments — 12 months

How risk drives the interval

The intervals in AS/NZS 3760 are not arbitrary — they are based on the rate at which damage accumulates in a given environment. A power tool on a construction site sees impact, dust, moisture and abrasion that a desktop power supply in an office never sees. Shorter intervals catch developing faults before they become hazards.

Your own risk assessment can shorten an interval, never lengthen it. If you have evidence that equipment is failing tests more frequently than expected, that is the signal to shorten the cycle.

New and out-of-the-box equipment

New equipment is required by AS/NZS 3760 to be visually inspected before first use and tagged with an 'inspected' indicator — it does not need to be electrically tested until its next routine interval. That visual inspection picks up shipping damage or factory faults before they put someone at risk.

Hire and loan equipment

Hire equipment carries an extra requirement — visual inspection before each hire — because it cycles through many users and environments in a year. The 12-month electrical test cycle still applies on top of the per-hire inspection.

RCDs and safety switches

Portable RCDs that protect site power tools are subject to push-button testing (typically daily on construction sites) and operating-time testing at the AS/NZS 3760 cycle. Fixed RCDs are tested under AS/NZS 3012 / AS/NZS 3760 depending on the installation.

What your asset register should contain

A workable register has, at minimum, an item identifier (asset number or description + serial), the test result, the test date, the next due date and the technician who tested it. Most quality systems also want the environment classification (so the interval can be defended) and any free-form notes.

How AmpTech runs test and tag in Perth

AmpTech runs scheduled test and tag rounds across Perth construction sites, factories, workshops and commercial offices. Each round includes the visual inspection, the AS/NZS 3760 electrical tests, a durable tag with the test and next-due dates, and an itemised register supplied as a PDF or in your asset-management system’s format. While we are on site we can collect any instruments due for calibration and return them from our Caversham lab — one supplier, one register, one invoice.

FAQ

FAQs

Is AS/NZS 3760 law?
AS/NZS 3760 is a standard, not a law. Workplace safety law (WHS legislation in most Australian states, including Western Australia) requires electrical equipment to be safe. AS/NZS 3760 is the technical document regulators and auditors reference as the way to meet that obligation for portable electrical equipment.
Do I have to test every three months on a construction site?
For portable electrical equipment used on a construction or demolition site, the recommended interval is 3 months. Principal contractors will typically refuse to admit equipment to the site without a current tag.
Does new equipment need to be tested before first use?
Under AS/NZS 3760, new equipment requires a visual inspection and an indicator tag before first use; it does not require a full electrical test until its next routine interval.
Can I extend a 12-month interval to 24 months?
No. AS/NZS 3760 intervals are maximums for the environment; they can be shortened on risk grounds but not lengthened.
Do I need to test double-insulated (Class II) equipment differently?
Yes — Class II equipment does not have an earth conductor to test, so the earth continuity test is omitted; the insulation resistance test is applied to accessible conductive parts. AmpTech selects the right test sequence for each item.